Attached below are test results and certification from the E84 Fire Tunnel Test.

Standard Test Method for
Surface Burning Characteristics of Building Materials
ASTM E84–26a
Terralon
Report Number 26–09007
Test Number 6371–2271
July 29, 2026
Roysons Corporation
Rockaway, New Jersey
Date Sample Received: July 13, 2026
Date Specimen Prepared: July 15, 2026
Date Test Performed: July 29, 2026
Date of Report: September 1, 2026
FORM VERSION: RF-CTC-ASTM-E84-2026 DATE: 01/28/2026 COPYRIGHT: RF-CTC-ASTM-E84-2026 © 2026 Commercial Testing Company, Inc.
Page 1 of 4
This report is a presentation of results of a surface flammability test on a material submitted by Roysons Corporation, Rockaway, New Jersey.
The test was conducted in accordance with the ASTM International fire-test-response standard E84–26a, Surface Burning Characteristics of Building Materials, sometimes referred to as the Steiner tunnel test. ASTM E84 is an American National Standard (ANSI) and has been approved for use by agencies of the Department of Defense. The ASTM E84 test method is the technical equivalent of ANSI/UL723 Standard. The test is applicable to exposed interior surfaces such as walls and ceilings. The test is conducted with the specimen in the ceiling position with the surface to be evaluated face down toward the ignition source. Thus, specimens shall either be self-supporting by its own structural quality, held in place by added supports along the test surface, or secured from the back side.
This standard is used to measure and describe the response of materials, products, or assemblies to heat and flame under controlled conditions, but does not by itself incorporate all factors required for fire hazard or fire-risk assessment of the materials, products, or assemblies under actual fire conditions.
The purpose of the test is to provide only the comparative measurements of surface flame spread and smoke development of materials with that of select grade red oak and fiber–reinforced cement board, Grade II, under specific fire exposure conditions with the smoke area of heptane used to establish the smoke-developed index. The test exposes a nominal 24-foot long by 20-inch wide test specimen to a controlled air flow and flaming fire adjusted to spread the flame along the entire length of a red oak specimen in 5 minutes. During the 10-minute test duration, flame spread over the specimen surface are measured and recorded. Test results are calculated relative to red oak, which has an arbitrary rating of 100, and fiber–reinforced cement board, Grade II, as referenced in Annex A3 of E84, which has a rating of 0. The 100 smoke-developed index is calculated using the smoke area of heptane.
The test results are expressed as Flame Spread Index and Smoke-Developed Index. The Flame Spread Index is defined in ASTM E176 as “a number or classification indicating a comparative measure derived from observations made during the progress of the boundary of a zone of flame under defined test conditions.” The Smoke-Developed Index, a term specific to ASTM E84, is defined as “a number or classification indicating a comparative measure derived from smoke obscuration data collected during the test for surface burning characteristics.” There is not necessarily a relationship between the two measurements.
The method does not provide for measurement of heat transmission through the surface tested, the effect of aggravated flame spread behavior of an assembly resulting from the proximity of combustible walls and ceilings, or classifying a material as noncombustible solely by means of a Flame Spread Index.
The zero reference and other parameters critical to furnace operation are verified on the day of the test by conducting a 10–minute test using 1/4–inch fiber–reinforced cement board, Grade II, as referenced in Annex A3 of E84. Periodic tests using NOFMA certified 23/32–inch select grade red oak flooring provide data for the 100 flame spread reference with heptane providing data for calculating the 100 smoke
developed index. These procedures are more fully described in Section 7of the E84 Standard.
The test sample, selected by the client, was identified as Terralon, a non–woven wallcovering. Three test panels, each measuring two feet wide by eight feet in length, were prepared by adhering the material to 1/4-inch thick fiber-cement board complying with ASTM Specification C1186 (Grade II) and passing ASTM Test Method E136, as referenced in Annex A3 of E84, using Roman® PRO–732 Extra Strength™
Clay Wallcovering Adhesive. The adhesive was applied to the smooth side of the cement board, the material placed into the adhesive, and rolled with a segmented roller. This method of sample preparation is described in E2404, Standard Practice for Specimen Preparation and Mounting of Textile, Paper or Polymeric (Including Vinyl) and Wood Wall or Ceiling Coverings, Facings and Veneers, to Assess Surface Burning Characteristics, Section 8.2 Wall or Ceiling Coverings Intended to be Applied Directly to a Noncombustible Wall or Ceiling Surface. After dead-stacking overnight, the prepared panels were transferred to storage racks and conditioned to equilibrium in an atmosphere with the temperature maintained at 71 ± 2°F and the
Page 2 of 4
relative humidity at 50 ± 5 percent. For testing, the panels were placed end-to-end on the ledges of the tunnel furnace and the test conducted with no auxiliary support mechanism.
The test results, calculated on the basis of observed flame propagation and the integrated area under the recorded smoke density curve, are presented below. The Flame Spread Index obtained in E84 is rounded to the nearest number divisible by five. Smoke-Developed Indices are rounded to the nearest number divisible by five unless the Index is greater than 200. In that case, the Smoke-Developed Index is rounded to the nearest 50 points. The rounding procedures are more fully described in Sections 9.1, 9.2, and X3 of the E84 Standard. The flame spread and smoke development data are presented graphically at the end of this report.
Specimen ignition over the burners occurred at 0.25 minute. Surface flame spread was observed to a maximum distance of 5.83 feet beyond the zero point at 3.53 minutes. The maximum temperature recorded during the test was 582°F. For information purposes, the actual (unrounded) Flame Spread and Smoke-Developed Indices were 22.2 and 17.0 respectively.
The Flame Spread Index and Smoke-Developed Index values obtained by ASTM E84 tests are frequently used by code officials and regulatory agencies in the acceptance of interior finish materials for various applications. The most widely accepted classification system is described in the National Fire Protection Association publication NFPA 101 Life Safety Code, where:
Class A, B, and C correspond to Type I, II, and III respectively in other codes. They do not preclude a material being otherwise classified by the authority of jurisdiction.
Commercial Testing Company, Inc. is an ISO/IEC 17025:2017 accredited testing laboratory whose scope includes ASTM E84 – Standard Test Method for Surface Burning Characteristics of Building Materials. National Voluntary Laboratory Accreditation Program – NVLAP Lab Code: 100120-0
Page 3 of 4
ASTM E 84 TEST DATA
Client: Roysons Corporation
Test Number: 6371-2271
Material Tested: Terralon
Date: July 29, 2026
Test Results:
Time to Ignition = 00.25 minutes
Maximum Flamespread Distance = 05.83 feet Time to Maximum Spread = 03.53 minutes
Flame Spread Index = 20
Smoke Developed Index = 15
Page 4 of 4